THT/WALL-F-100-4T-20 IE3 SODECA Smoke Extract Fans
Product parameters
| Product attributes | Attribute value | Filter product attributes |
|---|---|---|
| Brand: | SODECA | |
| Type: | Smoke Extract Fans | |
| Max. Air Flow: | 76160 m³/h | |
| Blade Tilt Angle: | 28 ° | |
| Installed Power: | 15 KW | |
| Maximum admissible current (A)-690V: | 16.03 A | |
| Maximum admissible current (A)-400V: | 27.8 A | |
| Noise: | 70 dB | |
| Speed: | 1460 RPM | |
| Series: | THT/WALL-F |
Product Overview
Dynamic wall-mount extractor fans with motorised opening system for connection to extract duct. Specially designed for the fast, effective exhaust of harmful smoke and gases in the event of fire. Suitable for installation in industrial buildings, stores or in any other type of building. Can be used for ambient ventilation.
Fan:
• Helicoidal casing support and fixing flange to allow easy wall anchorage and installation.
• Approved in accordance with standard EN 12101-3, with certifications no.: 0370-CPR-0305 (F400) and 0370-CPR-0973 (F300).
• Tubular casing in sheet steel with polyester resin anti-corrosive treatment.
• Variable angle impeller made of cast aluminium.
• Shielded power cable with EMC protection.
• Airflow direction from motor to impeller.
Extruded aluminum hatch:
• An extremely robust structure that is able to withstand severe weather changes.
• Designed to ensure watertightness.
• Aluminum profile with thermal bridge break.
• Central ceiling and structure equipped with high performance thermal insulation.
• Thermal resistance of the assembly less than 0.89 W/m²·K.
• Position indicators in both positions (open and closed).
• Upper and lower opening mounting versions.
• Manual opening system.
• Airborne acoustic insulation value according to UNE-EN ISO 10140-2: Rw = 27 (0;-2) dB.
Motor:
• Class H motors for S1 continuous operation and S2 emergency use. With ball bearings, IP55 protection and 1 or 2 speeds, depending on model.
• IE3 efficiency motors.
• Three-phase 230/400 V 50 Hz (up to 3 kW) and 400/690 V 50 Hz (powers greater than 3 kW).
• Maximum temperature of air to be carried: S1 -25 ºC +40 ºC continuous service, also suitable for warm climates with temperatures up to 50 ºC. S2 operation, 300 ºC/2h, 400 ºC/2h.
Actuator:
• Reliability greater than 20,000 dual cycles.
• Supply voltage at 230 V AC 50/60 Hz.
• Working temperature: -25 ºC +60 ºC.
• Protection at the leading edge when closing the hatch.
• The stop in the closed position is regulated by an electronic limit switch.
Hatch finish:
• Anti-corrosive in extruded aluminum.
• RAL 7016 supplied as standard. Any other RAL can be supplied on demand.
On request:
• Actuator with 24 V DC supply voltage.
Application scenarios
-

Distributed Ventilation System
The distributed ventilation system is a decentralized air treatment solution. Different from the traditional central ventilation system, it controls tSee more -

Harvest Storerooms
Fans play a core role in regulating temperature and humidity, inhibiting mildew, and ensuring grain quality in grain storage rooms. Their role is notSee more -

Fan Retrofit
Fan retrofit is an engineering practice to improve the comprehensive performance of the existing fan system in terms of efficiency, energy consumptionSee more -

Machinery and Systems
Industrial equipment and systems must be cooled continuously to ensure reliable operation. Fans are key components for heat dissipation, ventilation,See more

Rachel
We offer competitive product pricing. For fast support, send your email, phone, address, and the product model & quantity you want—we’ll reach out quickly!
We typically respond via email within one business day! You can also contact us at Anthony@icxsg.com





























































English
Français
Deutsch
Português
Español
русский
한국어
العربية
Italiano
Indonesia
Schweiz
Polski
Nederlands
ישראל - עברית
Perzisch
ไทย
日本語
ኢትዮ-አማርኛ
Việt Nam
Kiswahili
Srpski
Ελληνικά
简体中文