Application Occasions
Low-Voltage Distribution Protection
● CM3E distribution circuit breakers are suitable for AC 50/60Hz TN, TT, IT distribution systems, meeting the requirements for "Selection of Electrical Apparatus" in GB50054.
● The entire series provides reliable contact indication and isolation functions, satisfying the requirements for isolation devices in GB50054.
Motor Circuit Protection
● OM3E motor protection circuit breakers provide overcurrent protection for motor starters, cables, and motors. Their protection characteristics comply with GB/T 14048.4, and their application meets GB50055.
Residual Current Protection
● Operating time meets the requirements for graded coordination in GB 13955.
● Provides residual current protection solutions for AC 690V.
● Equipped with an automatic reclosing module to achieve residual current automatic reclosing function.
Switching Function
● Two mechanically and electrically interlocked circuit breakers, equipped with controllers, etc., enable automatic switching between two power sources (refer to CA1/CA1B/CA1W series Automatic Transfer Switching Equipment sample data).
### Product Overview
● The CM3 Molded Case Circuit Breaker (hereinafter referred to as the circuit breaker) is an upgraded product of the CM1 series launched by our company. The electronic CM3E series circuit breakers have six current rating frames: 100A, 250A, 400A, 630A, 800A, and 1250A, with currents ranging from 12.5A to 1250A.
● Based on the rated ultimate short-circuit breaking capacity (Icu), the circuit breakers are classified into four levels: Type C (Basic), Type L (Standard), Type M (Higher Breaking Capacity), and Type H (High Breaking Capacity).
● The entire series can be installed horizontally (sideways), vertically (upright), or flat.
● All circuit breakers in the series possess an isolation function, indicated by the symbol:
●1X
Circuit breakers comply with the following standards:
● IEC 60947-1 & GB/T 14048.1-2012 Low-voltage switchgear and controlgear - Part 1: General rules
● IEC 60947-2 & GB/T 14048.2-2008 Low-voltage switchgear and controlgear - Part 2: Circuit-breakers
● IEC 60947-4-1 & GB/T 14048.4-2010 Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters (including motor protection)
### Normal Service and Mounting Conditions
● Ambient air temperature: -5°C to +40°C;
● Altitude at the installation site not exceeding 2000 meters;
● Relative humidity of the air at the installation site does not exceed 50% at a maximum temperature of +40°C; higher relative humidity is permissible at lower temperatures, e.g., 90% at 20°C. Special measures should be taken for occasional condensation due to temperature changes;
● Pollution Degree: 3;
● Circuit breakers meet GB/T 2423.10 test requirements, capable of withstanding mechanical vibration with frequency 2Hz~13.2Hz, displacement ±1mm, and frequency 13.2Hz~100Hz, acceleration ±0.7g;
● Installation category of the main circuit: III; Installation category of other auxiliary and control circuits: II;
● Circuit breakers are suitable for electromagnetic environment A;
● Tropical humid type (TH type) circuit breakers meet GB/T 2423.4 and GB/T 2423.18 test requirements, capable of withstanding the effects of humid air, salt mist, oil mist, and mold;
● Circuit breakers should be installed in locations without explosion hazards, conductive dust, or conditions sufficient to corrode metal and damage insulation;
● Circuit breakers should be installed in locations free from rain and snow intrusion;
● Service Conditions:
● Circuit breakers meet the test requirements of GB/T 2423.1 and GB/T 2423.2. Ambient air temperature can be as low as -25°C (products for temperatures down to -40°C are available; please consult our company) and as high as +70°C (derating required above +40°C; see technical data in this catalog);
● Circuit breakers meet the requirements of GB/T 2423.4 Test Db (temperature +55°C, relative humidity 95%);
● Characteristics unaffected up to an altitude of 2500 meters (derating required above 2500m; see technical data in this catalog);
● Storage conditions: Ambient air temperature -25°C to +70°C.