Schneider ISFL630 3P Fuse Disconnector
Product parameters
| Product attributes | Attribute value | Filter product attributes |
|---|---|---|
| Brand: | Schneider | |
| Series: | Fupact ISFL | |
| Fuse Specifications: | NH3 | |
| On/Off Load Type: | Mixed load switching | |
| Handle Type: | - | |
| How It Works: | Frontal Operation | |
| Rated Current: | 630A | |
| Poles: | 3P | |
| Rated Voltage: | 380/415VAC | |
| Installation: | Base plate installation |
Series Overview
Series Overview
Fupact T Working Mode
- The Fupact T series products integrate the functions of control, isolation, and the disconnector base into one device. These functions can also be realized by using different components in a matching way.
- ISFT and ISFL of Fupact
ISFT Horizontal Disconnector - type Isolating Switch and ISFL Vertical Disconnector - type Isolating Switch Have the Following Functions:
- Load switching of the circuit. The speed and breaking capacity of this type of disconnector during operation are related to the specific operation situation of the operator.
- The fuse wire forms the breaking element of the disconnector.
- The fuse wire is installed in the fuse wire carrier.
- By operating the handle, the fuse wire carrier can operate the moving contact.
- When the fuse wire carrier is in the open position (OFF), isolation can be realized.
- With the help of DIN fuse - type industrial fuses (NH), it can provide short - circuit or overload protection for the power - failure circuit.
Solutions Combining Different Components
- By using the isolating switch that is easy to match and the fuse wires installed on different disconnectors, it can protect the power - failure circuit and the motor. The functions provided by each component are:
- Load switching of the circuit (opening and closing) and isolation (isolating switch).
- Short - circuit or overload protection (disconnector).
- Such a combination of components can realize the function of the Compact INS/INV 40 - 800A isolating switch.
Compliance with Standards
- Fupact T disconnectors and their accessories comply with the following international standards and regulations:
- IEC 60947 - 1: General rules.
- IEC 60947 - 3: Switches, disconnectors, isolating switches, and combinations of disconnectors.
- IEC 60947 - 5.1 and below: Control circuit devices and switching elements, automatic control elements.
- These standards and regulations are applicable in most countries in the world.
- Fupact T disconnectors and their accessories comply with European standards (EN 60947 - 1 and EN 60947 - 3).
- Fupact T is used in combination with industrial fuse wires and complies with the following standards:
- IEC 60269
- BS 88 (for Fupact GS)
- DIN43620/VDE0636
Environmental Endurance
- Fupact T disconnectors can meet all environmental requirements specified by the following standards:
- IEC/EN 60068 - 2 - 30: Damp heat test under air - conditioned conditions, 95% relative humidity at 55°C (damp heat temperature conditions).
- IEC/EN 60068 - 2 - 52: Salt spray test, KB hardness 2 - level test.
- IEC/EN 60068 - 2 - 56: Damp heat test under the condition that the equipment has not been operating for 48 hours, environmental category C2.
- In conclusion, the disconnector is suitable for all climatic environments.
Pollution Level
- Fupact T disconnectors are certified and can operate in an environment with a pollution level of 3, which complies with the IEC 60947 standard for industrial environments.
Ambient Temperature
- The operating temperature range of Fupact T disconnectors is - 20°C to + 70°C. When the temperature is higher than 40°C, the derating coefficient given must be used.
- The equipment must operate under the above ambient temperature conditions.
- The storage temperature range of Fupact T disconnectors with original packaging should be - 50°C to + 85°C.
Protection Class
- For Fupact disconnectors with terminal covers, their direct contact protection class complies with IEC 60529 (IP protection class) and IEC 62262 standards:
- With direct rotary handle: IP20/K07
- With extended rotary handle (Fupact GS): IP65/K10
- With extended rotary handle and padlock: IP65/K08
Contact Indication
- The IEC 60947 - 3 standard defines the isolation with contact indication as follows:
- The isolation position corresponds to the (OFF) position.
- Unless the main contact is actually open, otherwise the operating handle cannot indicate the OFF position.
- Unless the main contact is actually open, otherwise the handle cannot be locked in the OFF position.
- GS isolating switch disconnectors are suitable for isolation with contact indication.
- Installing an extension handle on GS will not change the nature of isolation.
- The mechanical type test certification of the isolation with contact indication function can ensure the following:
- The mechanical reliability of the contact indication system.
- There is no leakage situation.
- There is a voltage - withstanding capability between the incoming and outgoing line terminals.

Rachel
We offer competitive product pricing. For fast support, send your email, phone, address, and the product model & quantity you want—we’ll reach out quickly!
We typically respond via email within one business day! You can also contact us at Anthony@icxsg.com





























































English
Français
Deutsch
Português
Español
русский
한국어
العربية
Italiano
Indonesia
Schweiz
Polski
Nederlands
ישראל - עברית
Perzisch
ไทย
日本語
ኢትዮ-አማርኛ
Việt Nam
Kiswahili
Srpski
Ελληνικά
简体中文